Fire sensors
To connect fire sensors to the Omnia8 burglar Control panel:
1. Program a Control panel Zone as a Normally Open 24h Zone.
2. Connect to the sensor repeat output.
Figure 15 shows the connection of three rate-of-rise temperature or smoke
detectors Bentel RT-101, RT-102, RF501t.
+
- The ground of the detector lines is powered by auxiliary output 24[O2].
This output must be programmed as Normally Closed, otherwise, it will
not supply the Fire GND signal (refer to "PROGRAMMING").
- A 100 mA max. current can circulate on terminal 24[O2].
Figure 16 shows the connection with line L1 as balanced and relay base.
Output 24[O2] as Normally Closed.
Figure 15 Connection of fire sensors
Figure 16 Connection with a balanced line and relay base
26 Security System Control Panels Omnia8/Omnia4