Stop signalling devices
To stop the Alarm output (terminals [NO-COM-NC]):
1. Disarm all partitions.
2. Enter INSTALLER PIN (on any keypad).
3. Press .
The current telephone call will stop, and the call queue will be cleared.
Jumper 13 Signalling devices can also be stopped by short-circuiting the connector
pins 13 on the Main Unit board. It may also be useful to connect a keylock
switch, which will be able to stop the signalling devices in the event of trouble
on the communication bus, etc.
Open Main Unit
Before opening the Main Unit for servicing, testing etc., disable the Alarm
output by accessing the programming phase, as follows:
1. Enter INSTALLER PIN.
2. Press to access programming.
3. Open the Main Unit.
or
1. Enter MAIN USER PIN.
2. Press .
3. Press to access programming.
4. Open the Main Unit and service as required.
5. Close the Main Unit.
6. Press to quit.
INSTALLATION 31